Welcome to TRIPTI - The premier industrial
resource for air cooled & water cooled Chillers. We supply a broad range
of water chillers including standard package water chillers,
refrigeration cooled and portable water chillers. industrial water
chillers, as well as custom and temperature controlled water chillers.
Should you do a cost analysis, you would be pleasantly surprised to
realize how quickly a chiller ends up paying for itself and then saving
you money from there on out, for years to come.
Tripti are the manufacturers of aircooled
water chiller plants and water chilling plants ranging from
1 TR. to 40 TR. nominal cooling capacity for industrial applications
like laser chiller, medical chillers ,process chiller, machine cooling,
aquarium chiller etc.
Tripti range of Air Cooled recirculating Water chiller system
represents the ideal solution for the water cooling of Industrial
process Water chiller Systems & designed to facilitate quick
installation for all packaged chilled water system requirements.
Increased Production
The speed and accuracy of production
will increase as you maintain a constant and proper cooling temperature
in your equipment. A chiller will reduce the number of rejected parts
while increasing the number of parts produced per hour.
You may ask yourself: "Does my equipment shut down during summer
months?" -- "Are there periods where our rejection rate
increases?" A COOLING TOWER may provide adequate cooling during
winter months, but fail during the hotter periods of the year. A water
chiller will immediately eliminate this problem.
Why a Chiller ?
For Equipment Protection
The most compelling reason for a chiller is the protection it provides
to your valuable process equipment-- such as laser machines , spot
welders, injection molding equipment, and other applications. A chiller
commonly represents a small fraction of the cost of the processing
equipment, yet it provides solid protection of your investment, 24
hours a day, 7 days a week for years and years to come.
Sizing a Chiller Correctly
Simple instructions to Assure Proper
Cooling The importance of selecting a correctly sized Water chiller
cannot be downplayed. An undersized Water chiller will always be a
problem-- never able to properly cool the process equipment.
An oversize chiller will never be able to run at it's most efficient
level. Specify the correct size chiller and enjoy years of continuous,
efficient service. If you would like help, feel free to give us a call.
We do this all the time.
To size a water chiller properly you first need to calculate the delta T
( deg C) between the inlet and outlet water (the change in temperature),
and the rate of flow in liters per minute (LPM). Measuring the delta T
requires a thermocouple or thermometer.
Check the water temperature of the water inlet line and the water outlet
line, and subtract the numbers to compute how much heat the equipment is
adding to the water.
To measure the flow rate of the water place a flow meter on the outlet
line of your equipment. If one is not available, simply measure the time
it takes for the outlet flow to fill a twenty Litre bucket, and then
compute your Litre per minute (LPM) of flow.
Now that you have these two figures you need to calculate how many kcals
(kilo calories of heat Units) your equipment dissipates.
Here is the formula:
kcals/ hour = (the weight of water) LPM x Temperature Difference (delta
T)
Repeat this for all the equipment you have, and add up the total
kcals. Now that you have the kcals, lets compute the total Tons of
cooling you need from a chiller. 1 Ton of cooling is 3000 kcals/hour
hence.
Tons = (kcals/hr) / (12,000)
This is the minimum size unit you should need. Please keep another
20-25 % margin for There may be other circumstances, like
planning for expansion, that would lead you to buy a different size
unit. For more information about the specific units, please contact us.
Salient Features of Process Water Chiller
-
Compact skid mounted water chiller
system, ready to install.
-
Water Chillers are fully automatic
with tried & tested controls.
-
Quick chilling is ensured with plate
type or shell and tube evaporators.
-
Our water chillers use energy saving
with cycling fans and high efficiency fin tube aircooled condensers with
liberal sized fans.
-
Water Chillers offer Guaranteed
cooling capacity at rated parameters.
Applications of Industrial Air cooled Water Chiller
-
Chemical / Pharmaceutical process
water chilling.
-
Plastic Process chiller for :
Injection Molding, Blow Molding, (Mould Chiller) etc.
-
Extruders, PVC Pipes, Woven Sacks,
PP Film Lamination etc.
-
Calendars (Plastic & Rubber) Water
Chiller.
-
Milk and Dairy / Pasteurising, Food
Products.
-
Lubricants / hydraulic Oil Cooling
and Dewaxing of Oils.
-
Plating, Anodizing and Induction
heat treatment water chiller.
-
Pulp and Paper Processing.
-
Printing Ink / Paper Waxing cooling.
-
Bleaching / Dyeing Industry water
chiller.
-
EDM Machine cooling.
-
Concrete curing. Glazing
-
Comfort cooling.
-
Laser cooling
-
Process water chilling.
The Fine Quality Component Features
-
Hermetic / Semi hermetic sealed /
screw compressors with internal over load protection.
-
Air cooled condenser with copper
tubes and Aluminum fins.
-
Plate type / shell and tube
evaporator for high efficiency.
-
Stainless Steel storage tank with
external insulation to prevent moisture ingress and condensation.
-
Refrigerant circuit consists of
reputed filter dryer, thermostatic expansion valve / capillary, sight
glass, accumulator. and other controls from Danfos /Sporlan / Alco
-
Controls with safety devices - high
and low refrigerant switches, low water level, flow switch.
-
All Refrigerant tubing is high grade
copper.
-
Digital temperature indicator
controller for precise temperature controlling.
-
Audio visual indication for controls
and safeties.
-
Pumps suitable for high flow and
pressure.
-
Trolley mounting- optional.
Technical Specifications
|
|
Air-cooled Water Chillers |
|
S.
No. |
Model No. |
Nominal
Cooling Capacity |
Compressor
Power K.W |
Pump Power H.P |
Water Flow LPM |
|
Watts. |
TR. |
|
With
Sealed Reciprocating Compressor
|
|
1 |
TC
05 AC |
1750 |
0.5 |
0.7 |
0.25 |
10 |
|
2 |
TC
10 AC |
3500 |
1.0 |
1.4 |
0.50 |
15 |
|
3 |
TC
15 AC |
5250 |
1.5 |
1.7 |
0.75 |
25 |
|
4 |
TC
20 AC |
7000 |
2.0 |
2.4 |
1.00 |
35 |
|
5 |
TC
30 AC |
10500 |
3.0 |
3.2 |
1.00 |
50 |
|
6 |
TC
40 AC |
14000 |
4.0 |
4.1 |
1.50 |
60 |
|
7 |
TC
50 AC |
17500 |
5.0 |
6.0 |
1.50 |
70 |
|
8 |
TC
60 AC |
21000 |
6.0 |
6.7 |
1.50 |
80 |
|
9 |
TC 70 AC |
24500 |
7.0 |
7.5 |
2.00 |
90 |
|
10 |
TC 100 AC |
35000 |
10.0 |
10.1 |
3.00 |
120 |
|
11 |
TC 120 AC |
42000 |
12.0 |
12.7 |
3.00 |
150 |
|
With
Sealed Scroll Compressor |
|
12 |
TC
40 AC |
14000 |
4.0 |
4.0 |
1.50 |
60 |
|
13 |
TC
50 AC |
17500 |
5.0 |
4.8 |
1.50 |
70 |
|
14 |
TC
60 AC |
21000 |
6.0 |
5.3 |
1.50 |
80 |
|
15 |
TC
70 AC |
24500 |
7.0 |
6.5 |
2.00 |
90 |
|
16 |
TC
80 AC |
28000 |
8.0 |
7.3 |
2.00 |
100 |
|
17 |
TC
100AC |
35000 |
10.0 |
8.1 |
3.00 |
120 |
|
18 |
TC
120AC |
42000 |
12.0 |
10.7 |
3.00 |
150 |
| 19 |
TC
135AC |
47250 |
13.5 |
12.4 |
3.00 |
170 |
|
With
Semi-Sealed Reciprocating Compressor |
|
20 |
TC
155 AC |
54250 |
15.5 |
14.5 |
3.00 |
200 |
|
21 |
TC 200 AC |
70000 |
20.0 |
17.0 |
5.00 |
300 |
| 22 |
TC 230 AC |
80500 |
23.0 |
21.0 |
5.00 |
315 |
|
23 |
TC 250 AC |
87500 |
25.0 |
25.4 |
5.00 |
325 |
| 24 |
TC 300 AC |
105000 |
30.0 |
36.1 |
5.00 |
390 |
|
25 |
TC 350 AC |
122500 |
35.0 |
44.8 |
5.00 |
440 |
| 26 |
TC 400 AC |
140000 |
40.0 |
51.4 |
5.00 |
480 |
|
|